Tripp Lite SmartOnline SUT Series 3-Phase 208/120V 220/127V 60kVA 60kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option

  • Brand : Tripp Lite
  • Product name : SmartOnline SUT Series 3-Phase 208/120V 220/127V 60kVA 60kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option
  • Product code : SUT60K
  • GTIN (EAN/UPC) : 0037332186720
  • Category : Uninterruptible Power Supplies (UPSs)
  • Data-sheet quality : created/standardized by Icecat
  • Product views : 31456
  • Info modified on : 04 Oct 2022 15:06:55
  • Product Brochure/Datasheet (0.5 MB) Tripp Lite SUT60K user manual (37.3 MB)
  • Warranty: : 1 Year
  • Long product name Tripp Lite SmartOnline SUT Series 3-Phase 208/120V 220/127V 60kVA 60kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option :

    3-Phase, 208/120V, 220/127V, 60kVA, 60kW, On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option

  • Tripp Lite SmartOnline SUT Series 3-Phase 208/120V 220/127V 60kVA 60kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option :

    The SUT60K SmartOnline® SUT Series 3-Phase 208/120V 220/127V 60kVA 60kW On-Line Double-Conversion UPS provides complete protection against power interruptions and fluctuations that can contribute to equipment failures and data loss. It’s recommended for critical data center, telecommunications, computer network, light industrial and financial applications.

    The Voltage and Frequency Independent (VFI) design allows continuous operation at either 50 or 60 Hz. Zero transfer time from online to battery mode ensures no disruption to attached equipment loads. Offering an efficiency of 94% during normal operation and 98% in economy mode, the SUT60K reduces energy losses for cost-saving operation. Automatic bypass keeps connected equipment powered, even during overloads and many potential UPS fault conditions.

    IGBT inverter technology produces output power with less than 2% total harmonic distortion (THDi) to keep connected equipment functioning at its peak. A 3:1 crest factor safely supports a variety of loads, even those with wildly fluctuating power demands.

    Managing the SUT60K is simplified through the multi-language LCD interface, which displays critical operating conditions and diagnostic data, such as battery and load status. Four LEDs indicate AC, bypass, battery and fault modes. A built-in card slot supports optional remote management cards, such as WEBCARDLX, for comprehensive monitoring and control over a network.

  • Short summary description Tripp Lite SmartOnline SUT Series 3-Phase 208/120V 220/127V 60kVA 60kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option :

    Tripp Lite SmartOnline SUT Series 3-Phase 208/120V 220/127V 60kVA 60kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option, Double-conversion (Online), 60 kVA, 60000 W, 120 V, 220 V, 50/60 Hz

  • Long summary description Tripp Lite SmartOnline SUT Series 3-Phase 208/120V 220/127V 60kVA 60kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option :

    Tripp Lite SmartOnline SUT Series 3-Phase 208/120V 220/127V 60kVA 60kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option. UPS topology: Double-conversion (Online), Output power capacity: 60 kVA, Output power: 60000 W. Serial interface type: RS-232. Typical backup time at full load: 3.1 min, Typical backup time at half load: 9.6 min, Battery recharge time: 3.2 h. Form factor: Tower, Product colour: Black, Housing material: Steel. Width: 520.7 mm, Depth: 800.1 mm, Height: 1760.2 mm

Specs
Features
UPS topology Double-conversion (Online)
Output power capacity 60 kVA
Output power 60000 W
Input operation voltage (min) 120 V
Input operation voltage (max) 220 V
Input frequency 50/60 Hz
Output operation voltage (min) 120 V
Output operation voltage (max) 220 V
Maximum current 200 A
Surge energy rating 9220 J
Number of input phases 3
Number of output phases 3
Efficiency 99%
Input power factor 0.99
Output power factor 1
Crest factor 3:1
EMI/RFI noise filtering
Noise level 70 dB
Audible alarm(s)
Audible alarm modes Low battery alarm, Overload alarm
Country of origin China
Ports & interfaces
Serial interface
Serial interface type RS-232
Battery
Typical backup time at full load 3.1 min
Typical backup time at half load 9.6 min
Battery recharge time 3.2 h
Cold start

Design
Form factor Tower
Housing material Steel
Cooling type Active
Product colour Black
Display type LCD
LED indicators
Certification IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5
Operational conditions
Operating temperature (T-T) 0 - 40 °C
Storage temperature (T-T) -20 - 40 °C
Operating altitude 0 - 3000 m
Technical details
Sustainability certificates RoHS
Weight & dimensions
Width 520.7 mm
Depth 800.1 mm
Height 1760.2 mm
Weight 421.8 kg
Package width 765.6 mm
Package depth 1556.3 mm
Package height 2429 mm
Package weight 628.7 kg
Packaging data
Cables included Serial
Logistics data
Master (outer) case width 765.6 mm
Master (outer) case length 1556.3 mm
Master (outer) case height 2429 mm
Master (outer) case gross weight 628.7 kg
Products per master (outer) case 1 pc(s)
Other features
Battery type BP288VEBP
Similar products
Product code: OMNIVS1500XLCD
Stock:
Price from: 0(excl. VAT) 0(incl. VAT)
Product code: OMNISMART700TSU
Stock:
Price from: 0(excl. VAT) 0(incl. VAT)
Product code: SU16KRT-1TFTAA
Stock:
Price from: 0(excl. VAT) 0(incl. VAT)